Electromagnetic flowmeter(Insertion-type )
+
  • Electromagnetic flowmeter(Insertion-type )

Specifications

Insertion Type Electromagnetic flowmeter
Model GNST-YT-CRLLJ
Nominal diameter range DN 15 to 3000 (½ to 120")
Accuracy ±1.5%
Flow Velocity 0~1 to 0~10m/s, full range continuously adjustable within 1~10m/s
Medium Conductivity >50μs/cm
Max Working Pressure 1.6Mpa
Sensor Material Molybdenum-containing stainless steel 0Cr118Ni12Mo2Ti, Hastelloy C-276, Titanium Ti, etc.
Tube Material ABS
Max Medium Temp. ABS60℃
Degree of Protection  Complies with GB-08-84 Standard IP68
Transmission Distance Max. 50m, Customizable
Output Signal 0~10mA (load resistance 0~1kΩ);
4~20mA (load resistance 0~500Ω);
Frequency: 1~5KHz (load resistance 250~1.2kΩ)
Connection Method Flange ball valve connection, Threaded (screw) ball valve connection
Installation Method Straight pipe section: 15D upstream, 10D downstream

 

Product features

1.Insertion design allows non-stop installation/removal, simplifying maintenance on existing pipelines
2.Measurement unaffected by medium temperature, pressure, density, viscosity or conductivity (≥5 μS/cm)
3.Near-zero pressure loss and minimal energy consumption
4.Lower cost than standard electromagnetic flowmeters, ideal for large/medium pipelines
5.Advanced low-frequency excitation ensures stable zero point and strong anti-interference
6.Wide flow range (1–10 m/s) with linear output

Installation instructions

① Pre-installation
Verify delivery matches your order.
Measure and record dimension L2 (rod flush with fitting bottom).
② Installation – Insertion
Piping: Horizontal, ≥5DN upstream / ≥3DN downstream straight run; valve ≥3DN downstream. No vibration or wall defects.
Drill φ60–62 mm hole (clean, burr-free edges).
Weld mounting fitting (flush with pipe interior, leak-proof).
Prep sensor: Loosen 3 set screws, remove rod/probe (do not disconnect). Seal thread, install ball valve.
Reinsert rod, tighten nut to match pre-recorded L2.
③ Removal
Loosen 3 set screws, back off lock nut 1–2 turns.
Lift rod ~250 mm, close valve, then remove rod.

Installation site

Keywords:

Electromagnetic flowmeter(Insertion-type )

Related Downloads

Electromagnetic flowmeter(Insertion-type )
+
  • Electromagnetic flowmeter(Insertion-type )

Electromagnetic flowmeter(Insertion-type )

GENESITE Insertion Type Electromagnetic flowmeter(GNST-YT-CRLLJ) with an ultra-compact transmitter.Nominal diameter: max. DN 3000 (120"). It has the characteristics of strong anti-interference ability and stable signal transmission.

Applications

Water and Wastewater Treatment,Chemical Industry,Petrochemical Industry,Metallurgical Industry,Food and Beverage Industry,Pharmaceutical Industry,Pulp and Paper Industry,Municipal Engineering & Public Utilities

Get A Quote

If you have any suggestions, please leave a message or send an email to us, and we will reply to you within 1 working day after receiving the message email.

Submit

Related Products

900S Laboratory

We often call it a small sewage monitoring station because of its powerful analysis function .

TX100 Laboratory

The GNST-TX100 biotoxicity water quality detector can detect toxicity and ATP in two modes.

401 Silicate

The laboratory water quality tester is a beautifully designed colorimetric analysis instrument.

HY01 Oil in water Laboratory

The GNST-HY01 infrared spectrophotometer is used to determine the oil after the water
< 1234...42 >